四川中光防雷科技股份有限公司
Products
ZGG40-275/320/385/440(2+0)hs
General                                                                                 
         This series consists of MOV power modules and a base, and is used for second-level protection of L-PE and N-PE. It applies in low voltage AC power distribution systems, and is connected between the AC power supply and the equipment in parallel. It protects the equipment from impulse surge and transient overvoltage caused by the outside environment (such as lightning and EMI) or by the system (such as switching effects of the system, startup or shutoff of the inductance and capacitance loads).
Features                                                                                 
         1Anti-reverse plug
         2High discharge capacity, low residual voltage
         3Overheating protection
         4Failure indication and centralized remote signalling alarm dry contacts
         5Degree of protection IP20, flammability UL 94 V-0
Standards Complied                                                                             
         IEC 61643-11:2011 Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power systems - Requirements and test methods
         EN 61643-11:2012 Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power systems - Requirements and test methods
Technical Data                                                                       
Operating Environment
Temperature range –40°C to 80°C
Relative humidity range 5% to 95%
Altitude range –500 m to +4000 m
Technical Parameters
Model ZGG40-275(2+0)hs ZGG40-320(2+0)hs ZGG40-385(2+0)hs ZGG40-440(2+0)hs
SPD according to IEC 61643-1 Class Ⅱ
SPD according to EN 61643-11 Type 2
Max. continuous operating voltage UC  275 V AC 320 V AC 385 V AC 440 V AC
Operating frequency 50/60 Hz
Nominal discharge current In (8/20 μs) 20 kA
Max. discharge current Imax (8/20 μs) 40 kA
Voltage protection level Up  1.4 kV 1.6 kV 1.8 kV 2.2 kV
Max. backup fuse 80 A gL/gG
Connection mode In parallel
Protection mode L-PE、N-PE
Response time tA ≤25 ns
Cross-sectional area of connecting terminals Multi-core: 1.5 mm2 to 25 mm2, single-core: 1.5 mm2 to 35 mm2
Max. cross-sectional area of remote signalling terminals 1.5 mm2
Intensity of remote signalling alarm contact AC: 250 V/0.5 A   125 V/1 A    DC: 30 V/0.1 A
Torque: connecting terminal/remote signalling interface 2.5 N•m /0.25 N•m
Degree of protection of enclosure (IP code) IP 20
Installation system TN-S
Mounting location DIN 35 mm rail
Flammability UL 94 V-0
Circuit Diagram                                                                       

Configuration