ZGGS40-670PVs1 Modular Power Supply SPD consists of the MOV, flame retardant housing, and metal components, characterized by fire-retardant, over-current & over heat protection, and remote signalling alarm; It is installed on the PCB board, mainly used for secondary and tertiary surge protection in low voltage AC/DC power supply and distribution system and electrical equipment.
Features
Small volume, high discharge capacity, fast response, and no follow current.
Standards Complied
IEC 61643-11:2011 Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power systems – Requirements and tests
EN 61643-11:2012 Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power systems – Requirements and tests
UL1449 Ed.4 Standard for Surge Protective Devices
EN 50539-11: 2013 Low-voltage surge protective devices -Surge protective devices for specific application including d.c. -Part 11: Requirements and tests for SPDs in photovoltaic applications
Technical Data
Operating Environment
Temperature range |
-40 ℃~+85 ℃ |
Relative humidity range |
5 %~95 % |
Altitude range |
-500 m~﹢5000 m |
Technical parameters
Model |
ZGGS40-670PVs1 |
SPD according to IEC 61643-11:2011 |
Class Ⅱ |
SPD according to EN 61643-11:2012 |
Type 2 |
Number of ports |
One |
Maximum continuous operating voltage Uc |
510V AC |
Nominal discharge current In(8/20μs) |
20kA |
Max. discharge current Imax(8/20μs) |
40kA |
Voltage protection level UP |
2.3kV |
Max. backup fuse |
80A gL/gG |
Response time tA |
≤25 ns |
Remote signalling alarming mode |
Normal: closed; failure: open-circuit |
Intensity of remote signalling alarm contact |
30V DC, 0.1A; 125V AC,1A |
Method of mounting |
Welding to PCB |
Installation location |
Indoor |
Application system |
TN; TT, IT: L-N |
Degree of protection |
IP20 |
Flammability |
UL94V-0 |
Installing form |
Welding On board |
SPD according to EN 50539-11:2013 |
Type 2 |
Maximum continuous operating voltage UCPV |
670V DC |
Short-circuit current rating ISCPV |
1000A |
Nominal discharge current In(8/20μs) |
20kA |
Max. discharge current Imax(8/20μs) |
40kA |
Voltage protection level UP |
2.3kV |
Response time tA |
≤25ns |
Modes of protection |
+ — -, +/- —PE |
Application system |
Photovoltaic system |
Circuit Diagram
Configuration
Structure size PCB-hole drilling