四川中光防雷科技股份有限公司
Products
ZGGS40-60 Modular Power Supply SPD
General                                                                                 
         The ZGGS40-60 Modular Power Supply SPD consists of the MOV, flame retardant housing, and metal components, characterized by fire-retardant, over-current & overheat protection, and remote signalling alarm; it is installed on the PCB board, mainly used for secondary and tertiary surge protection in low voltage power supply and distribution system and electrical equipment.
Features                                                                                 
         Small-sized, high discharge capacity, high response speed and no flow current.
Standards Complied                                                                             
         IEC 61643-11:2011 Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power systems – Requirements and tests 
         EN 61643-11:2012 Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power systems – Requirements and tests
         YD/T1235.1-2002 Performance requirements for surge protective devices connected to low-voltage distribution systems of telecommunication stations/site
         YD/T 1235.2-2002 Testing methods for surge protective devices connected to low-voltage distribution systems of telecommunication stations/site
Technical Data                                                                             
Operating Environment
Temperature range -40 ℃~+85 ℃
Relative humidity range 5 %~95 %
Altitude range -500 m~+3000 m
Technical Parameters
Model ZGGS40-60
SPD according to IEC 61643-11:2011 ClassⅡ
SPD according to EN 61643-11:2012 Type2
Number of ports One
Max. continuous operating voltage UC 60 V AC 80 V DC
Nominal discharge current In(8/20μs) 20 kA
Max. discharge current Imax(8/20μs) 40 kA
Voltage protection level Up 500 V
Response time tA ≤25 ns
Mode of remote signal alarm Normal: closed; failure: open-circuit
Contact strength of remote signal alarm port 30 V DC, 0.1 A; 125 V AC,1 A
Method of mounting Welding to PCB
Installation location Indoor
Degree of protection IP 20 (After installation)
External dimensions 32.5 mm×14 mm×26 mm (L×W×H)
Flammability UL94 V-0
Installing form Welding On board
Circuit Diagram                                                                    
Configuration                                                                             

                 External dimensions drawing                                     Opening hole drawing