ZGGH20-275
General                                                                                 
         ZGGH20-275 Modular Power Supply SPD consists of a ZGGH20-275MK power module and a ZGGH20-DZ1 base, used for the secondary or tertiary protection of L -N and L /N-PE of AC systems. It is connected between the AC power supply and system equipment in series or in parallel. It can prevent the equipment from the impulse surge and transient overvoltage caused by the outside environment (such as lightning, EMI, etc.) or by the system (such as switching effects of the system, startup or shutoff of the inductance and capacitance load, etc.).
Features                                                                                 
         1Anti-reverse protection on the module;
         2Low residual voltage;
         3Overtemperature protection;
         4Failure indication and centralized remote signalling alarm dry contacts;
         5Enclosure IP20, UL94 V0.
Standards Complied                                                                             
         IEC 61643-1:2005 Low-voltage surge protective devices –Part 1:Surge protective devices connected to low-voltage power distribution systems –Requirements and tests
         UL 1449 Surge Protective Devices
Technical Data                                                                             
Operating Environment                                                                         
Temperature -40℃~80℃
Relative humidity 5 %~95 %
Altitude -500 m~﹢3000 m
Technical Parameters
Model ZGGH20-275
SPD according to IEC 61643-1 Class Ⅱ, Class Ⅲ
SPD according to EN 61643-11 Type 2, Type 3
Max. continuous operating voltage Uc  275V
Operating frequency 50/60 Hz
Nominal discharge current In (8/20μs) 10kA
Max. discharge current Imax (8/20μs) 20kA
Level Ⅱ voltage protection Up  L-N: 1.5kV; L/N-PE: 1.8kV
Compound wave Uoc                           20 kV
Limiting voltage (6kV 1.2/50μs, 3kA 8/20μs) L-N: 1.1kV; L/N-PE: 1.1kV
Level Ⅲ voltage protection Up                  L-N: 1.5kV; L/N-PE: 1.5kV
Rated load current IL    25A
Prepositioned fuse ≤25A gL/gG
Connection mode In series; In parallel
Protection mode L-N, L/N-PE
Response time  tA   L-N: ≤25ns; L/N-PE: ≤100ns
Cross-sectional area of connecting terminals Multicore: 0.2 mm2~2.5 mm2; single-core: 0.2 mm2~4 mm2
Cross-sectional area of the remote signalling interface (max.)  2.5 mm2
Intensity of the remote signalling alarm contact AC: 250V/0.75A   125V/3A    DC: 30V/2A
Torque: connecting terminal 1.0 N•m
Enclosure degree of protection (IP code) IP 20
Installation system TN
Dimensions 90 mm×18 mm×69 mm
(excluding remote signalling terminals)
Mounting on DIN 35 mm rail
Flammability UL 94 V-0