ZGG40-1000(3+1)
General
ZGG40-1000(3+1) is formed by connecting three MOV power modules and one GDT power module by bus, used for protection of L-PE. It is applied in low voltage AC power distribution system, and connected between the AC power supply and the equipment in parallel. It can prevent the equipment from the impulse surge and the transient overvoltage caused by the outside environment (such as lightning, EMI, etc.) or by the system (such as switching effects of the system, startup or shutoff of the inductance and capacitance load, etc.) .
Features
1High discharge capacity, low residual voltage.
2Overtemperature protection.
3Failure indication and centralized remote signalling alarm dry contacts.
4Enclosure IP20, UL94 V-0.
Standards Complied
IEC 61643-11:2011 Low-voltage surge protective device-part 11: surge protective devices connected to low-voltage power systems-Requirements and test
EN 61643-11:2012 Low-voltage surge protective device-part 11: surge protective devices connected to low-voltage power systems-Requirements and test
Technical Data
Operating Environment
Temperature range |
-40 ℃~﹢80 ℃ |
Relative humidity range |
5 %~95 % |
altitude range |
-500 m~﹢4000 m |
Technical Parameters
Model |
ZGG40-1000(3+1) |
SPD according to IEC 61643-11 |
Class Ⅱ |
SPD according to EN 61643-11 |
Type 2 |
Max. continuous operating voltage UC |
L-N:1000 V AC;N-PE:255 V AC |
Nominal discharge current In (8/20μs) |
L-N:20 kA;N-PE:100 kA |
Max. discharge current Imax (8/20μs) |
L-N:40 kA;N-PE:160 kA |
Voltage protection level Up |
L-N:4 kV;N-PE:2.5 kV;L-PE:5.5 kV |
Max. backup fuse |
80 A gL/gG |
Leakage current |
≤20 μA |
Connection mode |
parallel |
Protection mode |
L-PE |
Response time tA |
≤100 ns |
Cross-sectional Area |
Stranded: 1.5 mm2~25 mm2, Solid: 1.5 mm2~35 mm2 |
Max. Cross-sectional Area For Remote signalling terminals |
1.5 mm2 |
Intensity of Remote Signalling Alarm Contact |
AC: 250 V/0.5 A 125 V/1 A DC: 30 V/0.1 A |
Torque: Connecting Terminal/Remote Signalling Interface |
2.5 N•m /0.25 N•m |
Degree of Protection (IP Code) |
IP 20 |
Installation system |
TN、TT、IT |
Installation system |
90 mm×144 mm×68 mm (excluding remote signalling terminals) |
Dimensions |
DIN 35 mm rail |
Mounting on |
UL94 V-0 |
Circuit Diagram
Configuration