四川中光防雷科技股份有限公司
Products
ZGGB40-385(1+1)
General                                                                              
        The ZGGB40-385(1+1) Modular Power Supply SPD consists of three MOV power supply modules, one GDT power module, and a base. It provides second-level protection for L-N and N-PE and its operating status can be monitored remotely. It applies in low voltage AC power distribution systems, and is connected between the AC power supply and the equipment in parallel. It protects the equipment from impulse surge and transient overvoltage caused by the outside environment (such as lightning and EMI) or by the system (such as switching effects of the system, startup or shutoff of the inductance and capacitance loads).
Features                                                                             
        1.Anti-plug and mutual-plug protection
        2.No backup fuse needed
        3.High discharge capacity, low residual voltage 
        4.Overheating and over-current protection
        5.Failure indication and centralized remote signalling alarm dry contacts
Standard Complied                                                                   
        IEC 61643-11:2011 Low-voltage surge protective devices – Part 11: Surge protective devices connected to low-voltage power systems – Requirements and test methods
Technical Data                                                                       
Operating Environment
Temperature range –40°C to 80°C
Relative humidity range ≤ 95% (25°C)
Altitude range –500 m to 4000 m 
Technical Parameters
Model ZGGB40-385(1+1)
SPD according to IEC 61643-1 /11 Class II
SPD according to EN 61643-11 Type 2
Modes of protection L-N N-PE
Maximum continuous operating voltage Uc 385 V AC 255 V AC
Working frequency 50/60 Hz
Nominal discharge current In (8/20 μs) 20 kA
Maximum discharge current Imax (8/20 μs) 40 kA
voltage protection level Up 2.0 kV 1.5 kV
Follow current interrupting rating Ifi / 100 Arms
Access mode In parallel
Response time TA ≤25 ns
Cross-sectional area of the copper wire connected by the terminal Multi-core wire: 1.5 mm2-25 mm2, single-core wire: 1.5-35 mm2
Cross-sectional area of the copper wire connected by the remote signalling interface 0.5-1.5 mm2
Sensitivity of the remote signaling alarming contact AC: 125 V/0.5 A, DC: 30 V/0.1 A
Torque: Terminal/Remote signalling interface 2.5/0.25 Nm
Degree of protection of enclosure (IP rating) IP20
Application system TT, TN
Installation mode 35-mm guide rail
Flammability UL94 V-0
Circuit Diagram 
Configuration                                                                             