Model |
ZGGF50-385(4+0)AYc |
ZGGF50-385(3+0)AYc |
ZGGF50-385(2+0)AYc |
SPD according to IEC 61643-11 |
Class Ⅰ+ Class Ⅱ |
SPD according to EN 61643-11 |
Type 1+Type 2 |
Number of ports (connection mode) |
One port ( in parallel) |
Nominal operating voltage Uo |
230 V 50/60 Hz |
Max. continuous operating voltage UC |
385 V(L-PE, N-PE) 50/60 Hz |
385 V(L-PE) 50/60 Hz |
385 V(L-PE, N-PE) 50/60 Hz |
Type of LV systems |
TN-S |
TN-C |
TN |
Modes of protection |
L-PE, N-PE |
L-PE |
L-PE, N-PE |
Nominal discharge current In (8/20 μs) |
50 kA (L-PE, N-PE) |
50 kA (L-PE) |
50 kA (L-PE, N-PE) |
Impulse discharge current Iimp (10/350 μs) |
50 kA (L-PE, N-PE) |
50 kA (L-PE) |
50 kA (L-PE, N-PE) |
Quantity of electric charge Q |
25 As (L-PE, N-PE) |
25 As (L-PE) |
25 As (L-PE, N-PE) |
Specific energy W/R |
625 kJ/Ω (L-PE, N-PE) |
625 kJ/Ω (L-PE) |
625 kJ/Ω (L-PE, N-PE) |
Measured limiting voltage UL( at Iimp) |
≤0.8 kV (after 10 μs, L-PE, N-PE) |
≤0.8 kV (after 10 μs, L-PE) |
≤0.8 kV (after 10 μs, L-PE, N-PE) |
Voltage protection level Up |
2.5 kV (L-PE, N-PE) |
2.5 kV (L-PE) |
2.5 kV (L-PE, N-PE) |
Expected short circuit current of power supply Ip |
2 kA |
Follow current interrupt rating(peak) Ifi |
2 kA (at 385 V a.c.) (L-PE, N-PE) |
2 kA (at 385 V a.c.) (L-PE) |
2 kA (at 385 V a.c.) (L-PE, N-PE) |
Response time tA |
≤100 ns (L-PE, N-PE) |
≤100 ns (L-PE) |
≤100 ns (L-PE, N-PE) |
Leakage current |
≤3 mA ( L-PE, N-PE ) |
≤3 mA (L-PE) |
≤3 mA ( L-PE, N-PE ) |
Residual current IPE |
≤3 mA |
Ratings and characteristics for external disconnector |
500 A gL/gG |
Installation location |
Indoor |
Degree of protection |
IP 20 (after installation) |
Method of mounting |
35 mm DIN rail |
Indication of disconnector operation |
Green: OK; Off: Replace |
Cross-sectional area |
Stranded: 6 mm2 to 25 mm2 |
Torque: connecting terminal/Remote signalling interface |
2.5 Nm/0.25 Nm |
Remote signalling parameters |
Max. : 250V/0.1A ( a.c.) , min. : 12V/1mA ( a.c.)
Max. : 30V/0.1A ( d.c.) , min. : 12V/1mA ( d.c.) |
Cross-sectional area for remote signalling terminals |
0.15 mm2~1.3 mm2 |
Material of enclosure |
PC |
Flammability |
UL94 V0 |
Storage period |
2 years |
Guarantee period |
2 years |