ZGWJ1(TY) Network Switch Security Protector
General
Standards Complied: GB 18802.1-2002,GB/T18802.21-2004,Q/20184261-8.6-2006 and Q/20184261-8.7-2006.
The product has the function on power and signal protection. It can be used for security protection of computer networks, multimedia network switches, intelligent corridor switches of institutions, schools, enterprises and institutions, and also for security protection of hubs, routers, etc.
The product is designed as a standard 1 cascade port and provides protection for 24 user-ports.
Technical parameters
Power section
Operating voltage
V |
Max. continuous operating voltage
V |
Nominal breakover voltage
V |
Nominal discharge current
8/20μs
kA |
Max. discharge current
8/20μs
kA |
Limiting voltage
8/20μs
5kA
kV |
Protection mode |
220 |
385 |
620 |
5 |
10 |
≤1.4 |
L-PE
N-PE
L-N |
Signal section
Max. continuous operating voltage
V |
Transmission rate
bit/s |
Insertion loss
dB |
Protected objects |
Impulse limiting voltage (1)
10/700μs
V |
Impulse limiting voltage (2)
1.2/50μs (600V)
8/20μs (300A)
V |
Impulse discharge voltage
1kV/μs
V |
Impulse durability
1.2/50μs
8/20μs
Combination wave |
Connection mode |
L/L |
1,2,3,6/PE |
SE/PE |
L/L |
IN |
OUT |
5 |
100M |
≤3 |
1,2
3,6 |
≤30 |
≤50 |
≤600 |
6kV
3kA |
600V
300A |
RJ45 Socket |
Structure features
Use a standard 19-inch chassis that can be mounted directly on the rack or on the table
Dimension: 442mm×154mm×44mm
Weight: 2.2kg
Front panel
As shown in Fig.2, the front panel of the ZGWJ1(TY) network switch security protector has 50 RJ45 sockets. The lower row marks "1~25" as input ports, and the upper row marks "1~25" as output ports. “1” is a cascade port.
It is designed with a power indicator (green) and a degradation indicator (red).
Rear panel
As shown in Fig.3, the ZGWJ1 (TY) network switch security protector has two three-core power sockets on the rear panel. The socket with needle is the power input end including a power switch. Its input voltage is AC 220V. The socket with hole is the power output end, connected to the protected network switch power supply. In addition there is a local grounding PE terminal.