ZGP1-32-H8-FZ-H Uniphase Power Distribution Unit (PDU)
General
The Power Distribution Unit (PDU), due to its industrial-grade power distribution process design, delivers high levels of safety and reliability. Common and intelligent PDUs are widely used based on the importance of equipment distribution and power energy management in various data room systems.
The ZGP1 series PDU is mainly used for AC power distribution (including TT, TN, IT power distribution system) of system equipment in the cabinet of the equipment room. According to the power distribution power of the system equipment and the power distribution interface, the corresponding input and output interfaces are configured.
Features
1Support 16A current input.
2With working and lightning protection indicator functions.
3Aluminum profile black shell is adopted.
Technical Data
Operating Environment
Temperature range |
-5 ℃~45 ℃ |
Storage temperature |
-40 ℃~70 ℃ |
Storage humidity |
5%~95% RH |
Altitude range |
-500 m~﹢2000 m |
Technical Parameters
Model |
ZGP1-32-H8-FZ-H |
Number of input channels |
Single input |
Rated input voltage |
200 V~240 V |
Input power frequency |
50/60 Hz |
Maximum input current |
32 A |
Enter cable wire specifications |
3*6 mm2*3 m |
Number of output units |
8 bits |
Output socket system |
GB 5-hole socket |
Lightning protection function |
Green light: normal; Light off: no power on or lightning protection failure |
Overall dimension L*W*H |
482 mm*62 mm*47.2 mm |
Installation method |
Horizontal installation |
Shell material |
Aluminum profile metal shell |
Panel color |
Black |
Socket module |
Material: PA66 Flame retardant rating: meets UL 94 V-0 rating |
Environmental requirements |
RoHS |
Configuration
Standards Complied
YD/T 2063-2009 Distribution Unit (PDU) for Communication Equipment
GB 1002-2008 Single phase plugs and sockets for household and similar purposes, basic parameters and dimensions