ZGXM-M1J-5c Signal SPD
General
The ZGXM-M1J-5c signal SPD is used for protecting industrial control networks, automatic control and instrument lines, and data lines from lightning. This product uses two-stage protection to protect devices, that is, current release in the first stage and current clamping in the second stage. When a transmission line suffers lightning induction or surge attack, the SPD diverts lightning and surge current to ground, and clamps lightning and surge overvoltage to the scope allowed by the device.
Features
Easy installation: Terminal-based connection and guide rail-based installation
Hot-pluggable, compact size, high discharge capacity, fast response (ns), low protection level
Standards Complied
GB/T 18802.21-2016 Low-voltage surge protective devices – Part 21: Surge protective devices connected to telecommunications and signaling networks – Performance requirements and testing methods
Technical Data
Operating Environment
Temperature |
–40°C to 85°C |
Humidity |
≤ 90% (25°C) |
Altitude |
≤ 4000 m |
Technical Parameters
Rated voltage |
5 V |
Max. continuous operating voltage UC |
6 V DC |
Rated operating current IL (normal temperature) |
1 A |
Nominal discharge current In 8/20μs |
10 kA |
Total discharge current 8/20μs |
20 kA |
Impulse discharge current 10/350μs |
2.5 kA |
Voltage protection level (10/350μs) |
Line-Line |
≤ 26 V |
Line-PE |
≤ 40 V |
Voltage protection level (1 kV/μs) |
Line-Line |
≤11 V |
Line-PE |
≤ 11 V |
SE-PE |
≤ 600 V |
Internal Series resistance |
1.0 ohms |
Cut-off frequency |
100 MHz |
Capacitance |
≤ 30 pF |
Protected pin |
One pair of wires (1, 2), SE (4) |
Enclosure material |
PBT |
Torque: Terminal |
0.5 Nm |
Color |
Cold gray |
Degree of protection of enclosure (IP code) |
IP20 |
Fire resistance |
UL94 V-0 |
Circuit Diagram
Configuration
Dimensions (H x W x D): 69 mm x 93 mm x 12 mm