ZGG40-275/320/385/440(4+0)hs
General
This series is made up of MOV power modules and a base, used for secondary protection of L-PE, N-PE respectively. It is applied in low voltage AC power distribution system, and connected between the AC power supply and the equipment in parallel. It can prevent the equipment from the impulse surge and the transient overvoltage caused by the outside environment (such as lightning, EMI, etc.) or by the system (such as switching effects of the system, startup or shutoff of the inductance and capacitance load, etc.).
Features
1Anti-reverse plug .
2High discharge capacity, low residual voltage.
3Overtemperature protection.
4Failure indication and centralized remote signalling alarm dry contacts.
5Enclosure IP 20, UL 94 V-0.
Standards Complied
IEC 61643-11:2011 Low-voltage surge protective device-part 11: surge protective devices connected to low-voltage power systems-Requirements and test
EN 61643-11:2012 Low-voltage surge protective device-part 11: surge protective devices connected to low-voltage power systems-Requirements and test
Technical Data
Operating Environment
Temperature |
-40 ℃~80 ℃ |
Relative humidity |
5 %~95 % |
altitude |
-500 m~﹢4000 m |
Technical Parameters
Model |
ZGG40-275(4+0)hs |
ZGG40-320+0)hs |
ZGG40-385(4+0)hs |
ZGG40-440(4+0)hs |
SPD according to IEC 61643-11 |
Class Ⅱ |
SPD according to EN 61643-11 |
Type 2 |
Max. continuous operating voltage UC |
275 V AC |
320 V AC |
385 V AC |
440 V AC |
Operating frequency |
50/60 Hz |
Nominal discharge current In (8/20μs) |
20 kA |
Max. discharge current Imax (8/20μs) |
40 kA |
Voltage protection level Up |
1.4 kV |
1.6 kV |
1.8 kV |
2.2 kV |
Max. backup fuse |
80 A gL/gG |
Connection mode |
parallel |
Protection mode |
L-PE、N-PE |
Response time tA |
≤25 ns |
Cross-sectional Area |
Stranded: 1.5 mm2~25 mm2, Solid: 1.5 mm2~35 mm2 |
Max. Cross-sectional Area For Remote signalling terminals |
1.5 mm2 |
Intensity of Remote Signalling Alarm Contact |
AC: 250 V/0.5 A 125 V/1 A DC: 30 V/0.1 A |
Torque: Connecting Terminal/Remote Signalling Interface |
2.5 N•m /0.25 N•m |
Degree of Protection (IP Code) |
IP20 |
Installation system |
TN-S |
Mounting on |
DIN 35 mm rail |
Flammability |
UL94 V-0 |
Circuit Diagram
Configuration